HAHN & SOHN TECHNOLOGY

Hahn & Sohn C28NG petrol generator

Hahn & Sohn C28NG petrol generator
INTRODUCING THE MODEL

Hahn & Sohn C28NG petrol generator

Hahn & Sohn C28NG is a three-phase soundproofed natural gas generator with an output of 25 kVA (20 kW) in continuous operation and 28 kVA (22 kW) in standby operation. It is powered by a four-cylinder Cummins 4BT3.9-G36 engine, electricity is generated by a Stamford alternator, and…

Do you have questions about this product? We will respond within 24 hours.
+49 163 02 44 737  ·  info@hahn-sohn.eu
Mon–Fri 8:00–16:00
NON-BINDING ENQUIRY

The right model.
With expert advice.

Do you have questions about this product? We will respond within 24 hours. We will help you choose the necessary accessories.

+49 163 02 44 737info@hahn-sohn.eu

Mon–Fri 8:00–16:00 · Professional service

Your enquiry will be sent to info@hahn-sohn.eu. We use your details to respond to your enquiry.

Hahn & Sohn C28NG is a three-phase soundproofed natural gas generator with an output of 25 kVA (20 kW) in continuous operation and 28 kVA (22 kW) in standby operation. It is powered by a four-cylinder Cummins 4BT3.9-G36 engine, electricity is generated by a Stamford alternator, and operation is controlled by a ComAp InteliLite 4 AMF25 controller. The sound-insulated enclosure keeps the noise level at 72 dB at a distance of 7 m.

C28NG is a natural gas generator for locations where natural gas is available and three-phase 400 V / 50 Hz power is required. The Cummins 4BT3.9-G36 engine has 4 cylinders and a displacement of 3.9 l, and is turbocharged with charge air cooling. Rated speed is 1,500 rpm and engine speed is controlled by the engine control unit (ECU).

  • The electrical section consists of a single-bearing Stamford S0L2-M1/20KW alternator with brushless self-excitation, IP 23 protection, class H insulation, and voltage regulation accuracy of ±0.5%. The alternator has 12 leads.
  • Control is provided by the ComAp InteliLite 4 AMF25 with a 7-digit display, integrated speed governor and AVR. The controller monitors generator output (kW, kVA), protects against overload, and monitors start failure. The enclosure is fitted with an emergency stop button.
  • Directly on the machine are four industrial sockets mounted on a common rail: one blue and three red, labelled L1-L4. The switchboard contains a main CHINT 40 A four-pole circuit breaker with leakage current protection and a set of circuit breakers for the individual outputs. The enclosure is secured with locks, and the engine compartment is accessible from both sides.
  • The gas section of the engine compartment contains a solenoid valve, gas pressure regulator, pressure gauge, and gas detector with a digital display. The exhaust is fitted with insulation. The base frame has forklift pockets and lifting eyes for crane handling.
  • Gas consumption at continuous output: 10 m³/h at 100%, 8 m³/h at 75%, 5 m³/h at 50%, and 3 m³/h at 25% load.

Hahn & Sohn C28NG petrol generator

Why customers choose it

  • Natural gas operation - runs on natural gas from a fixed supply, with no need to refill diesel or petrol.
  • Cummins engine and Stamford alternator - branded components listed directly on the enclosure.
  • Three-phase 400 V output - suitable for workshops, construction sites, commercial premises, and backup power.
  • Quiet enclosure - 72 dB at 7 m.
  • ComAp AMF25 controller with display, protection functions, and emergency shutdown.
  • Industrial sockets directly on the machine and circuit breakers in a lockable switchboard.
  • 12-month or 1,000 operating-hour warranty on both the engine and alternator (whichever occurs first).

Practical tip

When planning the installation, allow for a weight of 1,016 kg and dimensions of 2,288 x 950 x 1,400 mm. The base frame has forklift pockets and lifting eyes. Connection to the gas supply and exhaust system should be carried out by an authorised specialist company.

Key features

  • Output 25 kVA / 20 kW (prime), 28 kVA / 22 kW (standby)
  • Fuel: natural gas
  • Voltage 400 V, 50 Hz, three-phase, rated current 36 A
  • Cummins 4BT3.9-G36 engine, 4 cylinders, 3.9 l, turbocharged with charge air cooling
  • Stamford S0L2-M1/20KW alternator, IP 23, class H insulation, AVR ±0.5%
  • ComAp InteliLite 4 AMF25 controller, 7-digit display
  • Noise level 72 dB at 7 m
  • 40 A main circuit breaker, sockets on the machine, emergency stop button
  • Gas detector, pressure regulator, and solenoid valve in the engine compartment
  • Warranty 12 months / 1,000 hours

Use / Installation / Operation

  • Designed for operation with a natural gas supply.
  • The machine is supplied as one complete unit on a frame designed for forklift and crane handling.
  • Installation of the gas supply, exhaust system, and connection to the electrical mains must be carried out by an authorised specialist company.
  • The installation, operating, and maintenance manual (safety instructions including risks associated with natural gas generators, installation, handling, commissioning, battery maintenance) is available for download from the product page.
  • Fluid capacities: engine oil 16.4 l, coolant (engine only) 10 l.

Additional parameters

Technical parameters

Category Backup generators
Warranty 1 yaer
Weight 1021 kg
Model C28NG
Fuel natural gas
Rated power 25 kVA / 20 kW
Standby power 28 kVA / 22 kW
Voltage 400 V (combined), 50 Hz, 3-phase
Rated current 36 A
Power factor 0,8
Noise level 72 dB @ 7 m
Engine Cummins 4BT3.9-G36
Engine specification 4-stroke, water-cooled, in-line, 4-cylinder, direct injection, turbocharged with intercooling
Engine capacity 3,9 l
Bore x stroke 102 x 120 mm
Compression ratio 10,5:1
Revolutions per minute 1,500 rpm (idling 750–850)
Speed control ECU
Ignition sequence 1-3-4-2
Starter motor 24 V
Gas consumption (prime) 10 / 8 / 5 / 3 m³/h at 100 / 75 / 50 / 25 per cent
Oil capacity 16,4 l
Coolant (engine only) 10 l
Maximum oil temperature 121 °C
Max. coolant temperature (standby / prime) 104 / 100 °C
Max. exhaust back pressure 10 kPa
Alternator Stamford S0L2-M1/20KW, single bearing, IP 23, H-class insulation, brushless
Voltage regulation accuracy ±0.5 per cent
Control unit ComAp InteliLite 4 AMF25
Dimensions (L x W x H) 2 288 x 950 x 1 400 mm

Dokumentace ke stažení

The right equipment starts with
expert advice.

We will help with selection, use and service. For every next step of your work.

Non-binding consultation
↑